Transformer Design - IEC Vs ANSI/IEEE
TRANSFORMERS DESIGN PARAMETERS IEC ANSI/IEEE For transformers up to 10 MVA, values of rated power roughly follow the R-10 series [3] given in ISO 3 (1997), preferred numbers : (…100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, etc.) Reference ANSI / NEMA C57 standard for power and distribution transformers, Standard ratings for different cooling methods OA / FA 55 / 650 C, and for standard impedance. Commonly International practice is to use Sealed tank transformers up to 1600 kVA and Conservator type for larger transformers American typical common practice in Petroleum & Chemical (P&C) applications is to use sealed tank transformers up to 15-20 MVA and conservator type for larger transformers. Shall be capable of sustaining a maximum of 105% rated Volts/Hz continuously without damage Shall sustain 110% Volts/Hz at no-load and shall be able to deliver rated power at 110% of the rated secondary voltage at a