Transformer Design - IEC Vs ANSI/IEEE










  

TRANSFORMERS DESIGN PARAMETERS
IEC
ANSI/IEEE
For transformers up to 10 MVA, values of rated power roughly follow the R-10 series [3] given in ISO 3 (1997), preferred numbers :
(…100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, etc.)
Reference ANSI / NEMA C57 standard for power and distribution transformers,
Standard ratings for different cooling methods OA / FA 55 / 650 C, and for standard impedance.
Commonly International practice is to use
Sealed tank transformers up to 1600 kVA and Conservator type for larger transformers
American typical common practice in Petroleum & Chemical (P&C) applications is to use sealed tank transformers up to 15-20 MVA and conservator type for larger transformers.
Shall be capable of sustaining a maximum of 105% rated Volts/Hz continuously without damage
Shall sustain 110% Volts/Hz at no-load and shall be able to deliver rated power at 110% of the rated secondary voltage at a power factor of at least 80% without overheating.
IEC gives no requirement for direction of power flow.
ANSI standards state that transformers shall be for step-down operation unless otherwise specified.
Transformers with a specified nominal impedance
³ 10% allowable tolerance ±  7.5%
Z < 10% allowable tolerance ± 10%
Allowable tolerance for the impedance of liquid filled transformers is ± 7%.
Number of shots of short-circuit withstand current is 3
Number of shots of short-circuit withstand current is 6 (first two shots are fully offset).
IEC 60076-5 (kVA)
Category I -              25-2500
Category II -            2501 – 100 000
Category III -           > 100 000
ANSI/IEEE C57.12.01(kVA)
Category I -           15-500
Category II -          501-5000
Category III -         5001-30 000
Each phase of transformer is subjected to a total 3 tests – in the position corresponding to high voltage,  Principal, Lower voltage tapping.
Each Phase of transformer shall be subjected to a total 6 tests –
4 times of symmetrical current and
2 times of asymmetrical current.
Duration of each test shall be 0.5 sec for category I. Duration of each test shall be 0.25 Sec for category II and III.
Duration of each test shall be 0.25 sec.



HIGHEST VOLTAGE Um (kV)
SHORT CIRCUIT APPARENT POWER
IEC
ANSI/IEEE
7.2; 12; 17.5 and 24
500
500
36
1 000
1 500
52 and 72.5
3 000
5 000
100 and 123
6 000
15 000



CONDITION
IEC 60076-1
ANSI/IEEE C57.12.00
Ambient Temperature
40 deg. C
40 deg. C
24 h average Temperature
-
30 deg. C
Monthly Average Temperature
30 deg. C
-
Yearly average Temperature
20 deg. C
-


Comments