Transformer Design - IEC Vs ANSI/IEEE
TRANSFORMERS DESIGN PARAMETERS
| |
IEC
|
ANSI/IEEE
|
For transformers up to 10 MVA, values of rated power roughly follow the R-10 series [3] given in ISO 3 (1997), preferred numbers :
(…100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, etc.)
|
Reference ANSI / NEMA C57 standard for power and distribution transformers,
Standard ratings for different cooling methods OA / FA 55 / 650 C, and for standard impedance.
|
Commonly International practice is to use
Sealed tank transformers up to 1600 kVA and Conservator type for larger transformers
|
American typical common practice in Petroleum & Chemical (P&C) applications is to use sealed tank transformers up to 15-20 MVA and conservator type for larger transformers.
|
Shall be capable of sustaining a maximum of 105% rated Volts/Hz continuously without damage
|
Shall sustain 110% Volts/Hz at no-load and shall be able to deliver rated power at 110% of the rated secondary voltage at a power factor of at least 80% without overheating.
|
IEC gives no requirement for direction of power flow.
|
ANSI standards state that transformers shall be for step-down operation unless otherwise specified.
|
Transformers with a specified nominal impedance
Z ³ 10% allowable tolerance ± 7.5%
Z < 10% allowable tolerance ± 10%
|
Allowable tolerance for the impedance of liquid filled transformers is ± 7%.
|
Number of shots of short-circuit withstand current is 3
|
Number of shots of short-circuit withstand current is 6 (first two shots are fully offset).
|
IEC 60076-5 (kVA)
Category I - 25-2500
Category II - 2501 – 100 000
Category III - > 100 000
|
ANSI/IEEE C57.12.01(kVA)
Category I - 15-500
Category II - 501-5000
Category III - 5001-30 000
|
Each phase of transformer is subjected to a total 3 tests – in the position corresponding to high voltage, Principal, Lower voltage tapping.
|
Each Phase of transformer shall be subjected to a total 6 tests –
4 times of symmetrical current and
2 times of asymmetrical current.
|
Duration of each test shall be 0.5 sec for category I. Duration of each test shall be 0.25 Sec for category II and III.
|
Duration of each test shall be 0.25 sec.
|
HIGHEST VOLTAGE Um (kV)
|
SHORT CIRCUIT APPARENT POWER
| |
IEC
|
ANSI/IEEE
| |
7.2; 12; 17.5 and 24
|
500
|
500
|
36
|
1 000
|
1 500
|
52 and 72.5
|
3 000
|
5 000
|
100 and 123
|
6 000
|
15 000
|
CONDITION
|
IEC 60076-1
|
ANSI/IEEE C57.12.00
|
Ambient Temperature
|
40 deg. C
|
40 deg. C
|
24 h average Temperature
|
-
|
30 deg. C
|
Monthly Average Temperature
|
30 deg. C
|
-
|
Yearly average Temperature
|
20 deg. C
|
-
|
Comments
Post a Comment